GKN+ 1 X 150/50 Curm 0.6/1 kV
GKN+ 1 X 150/50 Curm 0.6/1 kV
LV underground distibution single core cable with cross-linked HEPR insulation and concentric copper-wire conductor.
Read more- Nexans ref. : 10588149
- EAN : 7611755065515
Description
Description
Standards
-
ProductHD 603
-
NationalASE
Applications
- Underground distribution networks
- Pipe laying and ground laying
- Installation in electrical substations
Construction
- Copper conductor
- Cross-linked HEPR insulation
- Extruded filler
- Ceander concentric conductor made of copper wire
- Outer sheath in black 100% recycled PE, with 2 yellow longitudinal stripes
Properties
Outer sheath made from 100% recycled PE, specially abrasion-resistant and with a low shrinkage rate. Reduces the pulling force required by up to 30%, depending on the cross-section.
Copper conductor, 10.4% of which are recycled
New Metrium metering technology
Halogen-free
Reduces CO2 emissions by up to 10%.
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Conductor material
Copper
Conductor shape
Circular
Conductor flexibility
Stranded class 2
Insulation
HEPR
Core identification
Black
Material of the outer core / screen
Copper wires
Outer core type
Waveform concentric
Outer sheath
PE
Sheath colour
Black + 2 yellow lines
Halogen free
Yes
With Green/Yellow core
No
With smaller neutral conductor
No
Dimensional characteristics
Dimensional characteristics
Conductor cross-section
150 mm²
Conductor diameter
14.5 mm
Diameter over insulation
17.1 mm
Screen section
50 mm²
Diameter over external conductor / metallic screen
22.5 mm
Nominal outer diameter
26.0 mm
Approximate weight
207.3 kg/100m
Neutral conductor section (when smaller)
- mm²
Number of cores
1
Electrical characteristics
Electrical characteristics
Rated Voltage Uo/U (Um)
0,6/1 kV
Maximum operating voltage
1 kV
Perm. current rating in air 30°C - trefoil formation
410 A
Perm. current rating buried 20°C - trefoil formation
360 A
Nominal phase capacitance
0.48 µF / km
Impedance (AC) at max. operating temperature
0.159 Ohm
Phase reactance 50 Hz - trefoil formation
0.08 Ohm/km
Max. DC resistance of the conductor at 20°C
0.124 Ohm/km
AC resistance at 110°C, 60Hz
- Ohm/kft
I max. @ 60°C-buried, trefoil, joined, earthing 1pt, LF0.627
297.4 A
I max. @ 60°C-buried, trefoil, joined, earthing 1pt, LF1
276.6 A
I max. @ 60°C-in the air inside, flat, spaced, earthing 1pt, LF1
385.8 A
I max. @ 90°C-buried, trefoil, joined, earthing 1pt, LF0.627
384.9 A
I max. @ 90°C-buried, trefoil, joined, earthing 1pt, LF1
357 A
I max. @ 90°C-in the air inside, flat, spaced, earthing 1pt, LF1
556.6 A
Mechanical characteristics
Mechanical characteristics
Maximum pulling force by laying
9 kN
Usage characteristics
Usage characteristics
Bending factor when laying
12 (xD)
Bending factor when installed
10 (xD)
Maximum operating temperature
90 °C
Short-circuit max. conductor temperature
250 °C
Resources