Nexans GKN+ Cu single core
Nexans GKN+ Cu single core
Single-core LV underground distribution cables with cross-linked HEPR insulation and concentric copper-wire conductor made of recycled copper. With 100% recycled PE outer sheath and Metrium marking technology.
Read moreGKN+ 1 X 150/50 Curm 0.6/1 kV
Nexans ref. 10588149
- Packaging: m
- Conductor cross-section: 150 mm²
- Perm. current rating in air 30°C - trefoil formation: 410 A
- Perm. current rating buried 20°C - trefoil formation: 360 A
- I max. @ 60°C-buried, trefoil, joined, earthing 1pt, LF0.627: 297.4 A
- I max. @ 60°C-buried, trefoil, joined, earthing 1pt, LF1: 276.6 A
- I max. @ 60°C-in the air inside, flat, spaced, earthing 1pt, LF1: 385.8 A
- I max. @ 90°C-buried, trefoil, joined, earthing 1pt, LF0.627: 384.9 A
- I max. @ 90°C-buried, trefoil, joined, earthing 1pt, LF1: 357 A
- I max. @ 90°C-in the air inside, flat, spaced, earthing 1pt, LF1: 556.6 A
GKN+ 1 X 240/80 Curm 0.6/1 kV
Nexans ref. 10588150
- Packaging: m
- Conductor cross-section: 240 mm²
- Perm. current rating in air 30°C - trefoil formation: 550 A
- Perm. current rating buried 20°C - trefoil formation: 470 A
- I max. @ 60°C-buried, trefoil, joined, earthing 1pt, LF0.627: 400.7 A
- I max. @ 60°C-buried, trefoil, joined, earthing 1pt, LF1: 369.7 A
- I max. @ 60°C-in the air inside, flat, spaced, earthing 1pt, LF1: 528.8 A
- I max. @ 90°C-buried, trefoil, joined, earthing 1pt, LF0.627: 519.5 A
- I max. @ 90°C-buried, trefoil, joined, earthing 1pt, LF1: 477.7 A
- I max. @ 90°C-in the air inside, flat, spaced, earthing 1pt, LF1: 761.5 A
GKN+ 1 X 300/100 Curm 0.6/1 kV
Nexans ref. 10588151
- Packaging: m
- Conductor cross-section: 300 mm²
- Perm. current rating in air 30°C - trefoil formation: 630 A
- Perm. current rating buried 20°C - trefoil formation: 530 A
- I max. @ 60°C-buried, trefoil, joined, earthing 1pt, LF0.627: 452.9 A
- I max. @ 60°C-buried, trefoil, joined, earthing 1pt, LF1: 416.7 A
- I max. @ 60°C-in the air inside, flat, spaced, earthing 1pt, LF1: 612.9 A
- I max. @ 90°C-buried, trefoil, joined, earthing 1pt, LF0.627: 588.2 A
- I max. @ 90°C-buried, trefoil, joined, earthing 1pt, LF1: 539.4 A
- I max. @ 90°C-in the air inside, flat, spaced, earthing 1pt, LF1: 884.9 A
GKN+ 1x400 mm2 Cu rm/50 mm2 Cu K 1kV
Nexans ref.
- Packaging: m
- Conductor cross-section: 400 mm²
- Perm. current rating in air 30°C - trefoil formation: 840 A
- Perm. current rating buried 20°C - trefoil formation: 670 A
- I max. @ 60°C-buried, trefoil, joined, earthing 1pt, LF0.627: - A
- I max. @ 60°C-buried, trefoil, joined, earthing 1pt, LF1: - A
- I max. @ 60°C-in the air inside, flat, spaced, earthing 1pt, LF1: - A
- I max. @ 90°C-buried, trefoil, joined, earthing 1pt, LF0.627: - A
- I max. @ 90°C-buried, trefoil, joined, earthing 1pt, LF1: - A
- I max. @ 90°C-in the air inside, flat, spaced, earthing 1pt, LF1: - A
Description
Description
Standards
-
ProductHD 603; IEC 60228
-
NationalASE
Applications
- Underground distribution networks
- Pipe laying and ground laying
- Installation in electrical substations
Construction
- Copper conductor
- Cross-linked HEPR insulation
- Extruded filler
- Ceander concentric conductor made of copper wire
- Outer sheath in black 100% recycled PE, with 2 yellow longitudinal stripes
Properties
Outer sheath made from 100% recycled PE, specially abrasion-resistant and with a low shrinkage rate. Reduces the pulling force required by up to 30%, depending on the cross-section.
Copper conductor, 10.4% of which are recycled
New Metrium metering technology
Halogen-free
Reduces CO2 emissions by up to 10%.
Characteristics
Characteristics
Construction characteristics
Construction characteristics
With Green/Yellow core
No
With smaller neutral conductor
No
Dimensional characteristics
Dimensional characteristics
Neutral conductor section (when smaller)
- mm²
Number of cores
1