XKDT-Y 3x1x95 Alrm / 16 CuK mm² 12/20kV
XKDT-Y 3x1x95 Alrm / 16 CuK mm² 12/20kV
Three-core cables with aluminium conductors, cross-linked PE insulation (XLPE), copper-wire screens without outer protection sheath.
Conductor cross-sections 95 mm².
Read more- Nexans ref. : 10194925
- EAN : 7611755583170
Description
Description
Standards
-
ProductHD 620; IEC 60502
-
NationalASE
Applications
This family is designed for underground medium-voltage networks requiring good mechanical strength and a cost-effective solution:
- Underground distribution networks
- Installation in ducts and direct buried laying
- Electrical substations and MV installations
- Infrastructures requiring service continuity and reliability
Key advantages
- Robust XLPE insulation for high dielectric performance
- Excellent mechanical and environmental properties
- High durability for MV distribution networks
- Suitable for direct burial, ducts, and dedicated cable routes
- Halogen-free
- Assembly of three single-core cables
- Low-carbon aluminium, CO₂ footprint reduced by up to 40%
By choosing the XKDT Y – 12/20 kV three-core aluminium range, you select a reliable, robust, and durable cable designed to meet the requirements of modern medium-voltage networks.
admissible load MV cables
Currents are indicative and given for normal service conditions.
- Permanent charge 24h at 100% LF =1.0
- Conductor temperature 90 ° C
For cable laid in earth in tubes
- Depth of laying in soil : 1.0 m
- Max. soil temperatureempérature : 20 °C
- Soil thermal resistivity: 1.0 °C m/W
For cables placed in the open air
- Max. air temperature : 30 °C
- Protected from direct sunlight
- laid on consoles or cable trays
Grounding:
-
at one end, in this case the induced voltage increases proportionally with the length of the
the link.Attention, too high induced voltage can cause a breakdown of the outer sheath during overvoltages
transient. -
Either at both ends, which generates circulating currents and therefore more or less acceptable losses..
Correction factor
If the terms of service differ from those set out above, allowable currents must be corrected
taking into account all the correction factors that apply to the installation and service conditions encountered.
Main factors to consider are the following:
- Variable load, factor taking into account variable load, 10h to 100% and 14h to 60% LF= 0.627
- Operating temperature
- Ambient Temperature
- Thermal soil resistivity, factor taking into account the thermal resistivity of the soil in [°C * m / W]
- Magnetic armor
Our engineers are at your disposal to help and advise you.
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Dimensional characteristics
Dimensional characteristics
Electrical characteristics
Electrical characteristics
Mechanical characteristics
Mechanical characteristics
Usage characteristics
Usage characteristics