XDALT-YT 3x1x500 Cu/49 mm² 12/20 kV

Description

Description

Standards

  • Product
    HD 620; IEC 60502
  • National
    ASE

Applications

This family is designed for underground medium-voltage networks where effective earthing and a reliable screen are required:

  • Underground distribution networks
  • Installation in ducts and direct buried laying
  • Electrical substations and MV installations
  • Infrastructures requiring service continuity and reliability

Key advantages

  • XLPE insulation with high dielectric strength and low losses
  • Excellent mechanical and environmental properties
  • High durability for MV distribution networks
  • Suitable for direct burial, ducts, and dedicated cable routes
  • Radial watertightness ensured by bonded aluminium tape
  • Halogen-free
  • Assembly of three single-core cables
  • Outer sheath made of HDPE
  • 10.4% recycled copper / low-carbon aluminium, CO₂ footprint reduced by up to 40%

By choosing the XDALT YT – 12/20 kV three-core aluminium-screened range, you select a reliable, robust, and durable cable designed to meet the requirements of modern medium-voltage networks.

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor flexibility
Class 2
Conductor material
Copper
Conductor shape
Round compacted

Dimensional characteristics

Dimensional characteristics

Conductor cross-section
500 mm²
Conductor diameter
26.4 mm
Average insulation thickness
4.9 mm
Diameter over insulation
38.4 mm
Screen section
49 mm²
Diameter over external conductor / metallic screen
41.3 mm
Average sheath thickness
1.8 mm
Nominal outer diameter
102.5 mm
Approximate weight
1719.0 kg/100m
Number of cores
3

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
12/20 kV
Maximum operating voltage
24 kV
Max. DC resistance of the conductor at 20°C
0.037 Ohm/km
Calorific Power
207.4 MJ/m
I max. @ 60°C-buried, trefoil, joined, earthing 1pt, LF1
534 A
I max. @ 60°C-buried, trefoil, joined, earthing 2pts, LF1
521 A
I max. @ 60°C-in the air inside, trefoil, joined, earthing 1pt, LF1
686 A
I max. @ 60°C-in the air inside, trefoil, joined, earthing 2pts, LF1
671 A
I max. @ 90°C-buried, trefoil, joined, earthing 1pt, LF1
694 A
I max. @ 90°C-buried, trefoil, joined, earthing 2pts, LF1
680 A
I max. @ 90°C-in the air inside, trefoil, joined, earthing 1pt, LF1
994 A
I max. @ 90°C-in the air inside, trefoil, joined, earthing 2pts, LF1
976 A
Impedance at 50Hz and 90°C
0.1 Ohm/km
Nominal inductance
0.29 mH/km
Nominal phase capacitance
0.445 µF / km
Permissible short circuit current conductor 0.5s
101.7 kA
Permissible short circuit current conductor 1s
72.1 kA
Permissible short circuit current screen 0.5s
9.8 kA
Permissible short circuit current screen 1s
7.5 kA
Phase reactance 50 Hz - trefoil formation
0.094 Ohm/km

Mechanical characteristics

Mechanical characteristics

Maximum pulling force by laying
60 kN

Usage characteristics

Usage characteristics

Minimum installation temperature
-5 °C
Bending factor when laying
12 (xD)
Bending factor when installed
8 (xD)
Maximum operating temperature
90 °C
Short-circuit max. conductor temperature
250 °C

Resources

Resources

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close