GKN+ Flex 3x50/50 mm2 Cu

Description

Description

Standards

  • Product
    HD 603; IEC 60228
  • National
    ASE

Applications

This family is designed for underground low-voltage networks requiring high reliability:

Underground low-voltage distribution networks

  • Installation in ducts, cable trenches, cable trays and direct burial
  • Electrical substations
  • Infrastructure requiring service continuity and reliability

Key advantages

  • Class 5 copper conductors
  • 100% recycled sheath, significantly reducing environmental impact
  • 10.4% recycled copper in the conductor
  • Reduces CO₂ emissions by 9% to 17%
  • HEPR insulation providing excellent mechanical and thermal performance
  • Full transparency through the PEP Ecopassport
  • Low sheath shrinkage / high abrasion resistance
  • Halogen-free

By choosing the GKN+ Flex Cu three-core cable, you opt for a durable, high-performance cable aligned with modern carbon footprint reduction requirements without compromising reliability.

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Copper
Conductor shape
Circular
Conductor flexibility
Class 5
Insulation
HEPR
Number of conductors
3
Core identification
Black, red, white
Material of the outer core / screen
Copper wires
Outer core type
Waveform concentric
Outer sheath
PE
Sheath colour
Black + 2 yellow lines
Halogen free
Yes

Dimensional characteristics

Dimensional characteristics

Conductor cross-section
50 mm²
Conductor diameter
9.3 mm
Diameter over insulation
11.1 mm
Screen section
50 mm²
Diameter over external conductor / metallic screen
29.7 mm
Nominal outer diameter
33.1 mm
Approximate weight
249.1 kg/100m
Neutral conductor section (when smaller)
- mm²

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
0,6/1 kV
Maximum operating voltage
1 kV
Nominal phase capacitance
0.258 µF / km
Impedance (AC) at max. operating temperature
0.393 Ohm
Phase reactance 50 Hz - trefoil formation
0.073 Ohm/km
Max. DC resistance of the conductor at 20°C
0.386 Ohm/km
Perm. current rating buried 20°C - trefoil formation
170 A
Perm. current rating in air 30°C - trefoil formation
200 A
I max. @ 60°C-buried, trefoil, joined, earthing 1pt, LF0.627
138 A
I max. @ 60°C-buried, trefoil, joined, earthing 1pt, LF1
131 A
I max. @ 60°C-in the air inside, flat, spaced, earthing 1pt, LF1
140 A
I max. @ 90°C-buried, trefoil, joined, earthing 1pt, LF0.627
177 A
I max. @ 90°C-buried, trefoil, joined, earthing 1pt, LF1
168 A
I max. @ 90°C-in the air inside, flat, spaced, earthing 1pt, LF1
200 A

Mechanical characteristics

Mechanical characteristics

Maximum pulling force by laying
6 kN

Usage characteristics

Usage characteristics

Bending factor when laying
8 (xD)
Bending factor when installed
4 (xD)
Maximum operating temperature
90 °C
Short-circuit max. conductor temperature
250 °C
Minimum installation temperature
-5 °C

Resources

Resources

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close