GKN+-ALU 1 X 240 Alrm/50 Cu 0.6/1 kV

Description

Description

Standards

  • Product
    HD 603; IEC 60228
  • National
    ASE

Applications

  • Underground distribution networks
  • Pipe laying and ground laying
  • Installation in electrical substations

Construction

  • Aluminium conductor
  • Cross-linked HEPR insulation
  • Extruded filler
  • Concentric copper wire conductor
  • Outer sheath in black 100% recycled PE, with 2 yellow longitudinal stripes

Properties

Outer sheath made from 100% recycled PE, specially abrasion-resistant and with a low shrinkage rate. Reduces the pulling force required by up to 30%, depending on the cross-section.
With low-carbon aluminium conductor
New Metrium metering technology
Halogen-free

Reduces CO2 emissions by 40% to 43%.

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Aluminum
Conductor shape
Circular
Conductor flexibility
Stranded class 2
Insulation
HEPR
Core identification
Black
Material of the outer core / screen
Copper wires
Outer core type
Waveform concentric
Outer sheath
PE
Sheath colour
Black + 2 yellow lines
Halogen free
Yes
With Green/Yellow core
No
With smaller neutral conductor
No

Dimensional characteristics

Dimensional characteristics

Conductor cross-section
240 mm²
Conductor diameter
18.3 mm
Diameter over insulation
21.5 mm
Screen section
50 mm²
Diameter over external conductor / metallic screen
27.9 mm
Nominal outer diameter
31.7 mm
Approximate weight
165.2 kg/100m
Neutral conductor section (when smaller)
- mm²
Number of cores
1

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
0,6/1 kV
Maximum operating voltage
1.2 kV
Perm. current rating in air 30°C - trefoil formation
450 A
Perm. current rating buried 20°C - trefoil formation
380 A
Nominal phase capacitance
- µF / km
Impedance (AC) at max. operating temperature
- Ohm
Phase reactance 50 Hz - trefoil formation
0.07 Ohm/km
Max. DC resistance of the conductor at 20°C
0.125 Ohm/km
I max. @ 60°C-buried, flat, spaced, earthing 1pt, LF1
- A
I max. @ 60°C-buried, trefoil, joined, earthing 1pt, LF0.627
313.3 A
I max. @ 60°C-buried, trefoil, joined, earthing 1pt, LF1
289.1 A
I max. @ 60°C-in the air inside, flat, spaced, earthing 1pt, LF1
411.3 A
I max. @ 90°C-buried, trefoil, joined, earthing 1pt, LF0.627
405 A
I max. @ 90°C-buried, trefoil, joined, earthing 1pt, LF1
372.5 A
I max. @ 90°C-in the air inside, flat, spaced, earthing 1pt, LF1
591 A

Mechanical characteristics

Mechanical characteristics

Maximum pulling force by laying
7.2 kN

Usage characteristics

Usage characteristics

Bending factor when laying
12 (xD)
Bending factor when installed
10 (xD)
Maximum operating temperature
90 °C
Short-circuit max. conductor temperature
250 °C

Resources

Resources

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close