Cable HS XKDCu(Al)T 1000 mm² Cu 132 kV
Cable HS XKDCu(Al)T 1000 mm² Cu 132 kV
The XKDCuT / XKDAlT cable family is designed to ensure reliable and long-lasting power transmission in high-voltage networks. Thanks to their XLPE insulation, excellent dielectric performance and high mechanical resistance, these cables deliver optimal performance in underground networks, substations and critical energy infrastructures.
Read more- Nexans ref. : XKDCu(Al)T 1000 Cu 132 kV
Description
Description
Standards
-
TestIEC 60840; IEC 62067
-
NationalHD 632 Section O
Applications
This cable family is designed for strategic underground high-voltage links requiring very high reliability:
- Underground high-voltage distribution networks
- Installation in ducts, galleries or directly buried
- Electrical substations and transformer stations
- Infrastructures requiring service continuity and maximum safety
- Critical industrial and energy applications
Key benefits
- High-performance XLPE insulation ensuring excellent dielectric strength
- Very good mechanical and environmental resistance
- Radial and longitudinal water blocking to prevent moisture propagation
- Robust HDPE sheath with low shrinkage rate
- High durability for long-distance HV networks
- Solution suited to strategic infrastructures
By choosing this range of high-voltage cables, you opt for a reliable, robust and durable solution, perfectly suited to the requirements of modern HV networks.
Characteristics
Characteristics
Dimensional characteristics
Dimensional characteristics
Conductor cross-section
1000 mm²
Conductor diameter
39.1 mm
Diameter over insulation
76.1 mm
Outer Diameter
89.6 mm
Screen section
95 mm²
Approximate weight
14.7 kg/m
Electrical characteristics
Electrical characteristics
Operating voltage
132 kV
Permissible short circuit current screen 1s
15.0 kA
Permissible short circuit current conductor 1s
143 kA
Max. DC resistance of the conductor at 20°C
0.018 Ohm/km
Nominal phase capacitance
0.234 µF / km
I max. @ 90°C-buried in trefoil joined
1150 A
I max. @ 90°C-buried in trefoil spaced
1185 A
I max. @ 90°C-buried in flat formation joined
1030 A
I max. @ 90°C-buried in flat formation spaced
1180 A
I max. @ 75°C-buried in trefoil joined
1030 A
I max. @ 75°C-buried in trefoil spaced
1060 A
I max. @ 75°C-buried in flat formation joined
920 A
I max. @ 75°C-buried in flat formation spaced
1055 A
Load factor
1
Sheaths grounding
1 point
Thermal soil resistivity dry zone
0.85 °K.m/W
Mechanical characteristics
Mechanical characteristics
Maximum tensile load during service (Tl)
4000.0 daN
Usage characteristics
Usage characteristics
Max. conductor temperature in service
90 °C
Short-circuit max. conductor temperature
250 °C
Ambient ground temperature
20 °C
Laying operation bending radius
3200 mm
Laying depth, center of system
1000 mm
Laying tube diameter
150 mm
Distance between tubes (X)
220 mm