FE05-C 5X25 RM GB 3LNPE FLEX
Certifications and labels
FE05-C 5X25 RM GB 3LNPE FLEX
FE05-C Flex NOflamm® is a flexible, halogen-free safety cable specifically designed to ensure high fire protection in sensitive environments. Water-resistant (AD8) and featuring a robust construction, it provides reliable and long-lasting installation in buildings, tunnels and infrastructures where personal safety and service continuity are essential.
Read more- Nexans ref. : 10570598
- EAN : 7611755672294
Description
Description
Standards
-
ProductEN 50575; EN 60529; IEC 60228
-
TestEN 60754-2; IEC 60332-1-2; IEC 61034
-
NationalSEV TP 20B/3C-d
Applications
FE05-C Flex NOflamm® cable is intended for installations requiring a very high level of fire safety:
- Electrical installations in buildings and public infrastructures
- Technical rooms and sensitive areas
- Escape routes
- Fixed circuits up to 0.6/1 (1.2) kVac or 0.9/1.5 (1.8) kVdc
- Environments requiring low smoke emission and halogen-free materials
Key benefits
- Water-resistant (AD8), suitable for humid environments
- Highly flexible (class 5) for easy installation
- Robust construction with XLPE insulation
- Halogen-free: low smoke emission
- Rated voltage 0.6/1 kV
- CPR class Cca s1,d1,a1
By choosing FE05-C Flex NOflamm®, you opt for a reliable, safe and durable cable, perfectly suited to the most demanding professional installations.
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Conductor flexibility
Class 5
Conductor material
Copper
Conductor shape
Round compacted
Insulation
XLPE
Outer sheath
HFFR (Halogen Free Flame Retardant)
Sheath colour
Yellow
With Green/Yellow core
Yes
With smaller neutral conductor
No
Dimensional characteristics
Dimensional characteristics
Number of cores
5
Conductor cross-section
25 mm²
Approximate weight
1741 kg/km
Neutral conductor section (when smaller)
- mm²
Nominal outer diameter
27.4 mm
Electrical characteristics
Electrical characteristics
Maximum operating voltage
1000 V
Rated Voltage Uo/U (Um)
0,6/1 kV
Test voltage
3500 V
Mechanical characteristics
Mechanical characteristics
Maximum pulling force by laying
- kN
Usage characteristics
Usage characteristics
Bending factor when installed
- (xD)
Maximum operating temperature
- °C
Minimum installation temperature
-5 °C
Minimum operating temperature
-20 °C
Minimum static operating bending radius
- mm
RoHS conform
-
Short-circuit max. conductor temperature
- °C
U.V resistance
-
Water proof
AD8 according to UNE-EN 50525-2-21
Weather resistance
Low
Fire safety characteristics
Fire safety characteristics
Fire load
- MJ/km
Fire retardant
-
Flame retardant
EN 60332-1-2
Halogen free
Yes
Smoke density
EN 50399
Resources
Resources
Declaration of Performance
- Declaration of Performance n° : 1001053-CHCD
- Certification Date : 3/1/23
- AVCP (Assessment and Verification of Constancy of Performance) : System 1+
- Notified body : 2658
- Declared performance : Cca-s1,d1,a1
Our websites
Select your country to find our products and solutions
-
Africa
- Africa
- Ghana
- Ivory Coast
- Morocco
- North West Africa
- Americas
- Asia
- Europe
- Oceania