GKN+ 1x400 mm2 Cu rm/50 mm2 Cu K 1kV

Description

Description

Standards

  • Product
    HD 603
  • National
    ASE

Applications

  • Underground distribution networks
  • Pipe laying and ground laying
  • Installation in electrical substations

Construction

  • Copper conductor
  • Cross-linked HEPR insulation
  • Extruded filler
  • Ceander concentric conductor made of copper wire
  • Outer sheath in black 100% recycled PE, with 2 yellow longitudinal stripes

Properties

Outer sheath made from 100% recycled PE, specially abrasion-resistant and with a low shrinkage rate. Reduces the pulling force required by up to 30%, depending on the cross-section.
Copper conductor, 10.4% of which are recycled
New Metrium metering technology
Halogen-free
Reduces CO2 emissions by up to 10%.

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Copper
Conductor shape
Circular
Conductor flexibility
Stranded class 2
Insulation
HEPR
Core identification
Black
Material of the outer core / screen
Copper wires
Outer core type
Waveform concentric
Outer sheath
PE
Sheath colour
Black + 2 yellow lines
Halogen free
Yes
With Green/Yellow core
No
With smaller neutral conductor
No

Dimensional characteristics

Dimensional characteristics

Conductor cross-section
400 mm²
Conductor diameter
23.4 mm
Diameter over insulation
27.1 mm
Screen section
50 mm²
Diameter over external conductor / metallic screen
33.3 mm
Nominal outer diameter
36.7 mm
Approximate weight
449.0 kg/100m
Neutral conductor section (when smaller)
- mm²
Number of cores
1

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
0,6/1 kV
Maximum operating voltage
1 kV
Perm. current rating in air 30°C - trefoil formation
840 A
Perm. current rating buried 20°C - trefoil formation
670 A
Nominal phase capacitance
0.66 µF / km
Impedance (AC) at max. operating temperature
0.064 Ohm
Phase reactance 50 Hz - trefoil formation
0.053 Ohm/km
Max. DC resistance of the conductor at 20°C
0.047 Ohm/km
AC resistance at 110°C, 60Hz
- Ohm/kft
I max. @ 60°C-buried, trefoil, joined, earthing 1pt, LF0.627
- A
I max. @ 60°C-buried, trefoil, joined, earthing 1pt, LF1
- A
I max. @ 60°C-in the air inside, flat, spaced, earthing 1pt, LF1
- A
I max. @ 90°C-buried, trefoil, joined, earthing 1pt, LF0.627
- A
I max. @ 90°C-buried, trefoil, joined, earthing 1pt, LF1
- A
I max. @ 90°C-in the air inside, flat, spaced, earthing 1pt, LF1
- A

Mechanical characteristics

Mechanical characteristics

Maximum pulling force by laying
24 kN

Usage characteristics

Usage characteristics

Bending factor when laying
12 (xD)
Bending factor when installed
10 (xD)
Maximum operating temperature
90 °C
Short-circuit max. conductor temperature
250 °C

Resources

Resources

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close