Description
FIRE RESISTANT
Standards
International : EN 45545 - HL3; EN 50200; EN 50264-3-1; IEC 60228; IEC 60331-2; IEC 60331-21Description
Applications
FLAMEX® EN50264-3-1 4GKW FR flexible power cables maintain circuit integrity in case of fire (according to EN 50200 for 90 minutes) and are fire retardant, low smoke and halogen-free safisfying performance requirements of EN 45545-2-HL3.
On top of that, FLAMEX® cables withstand tough working conditions (oil, ozone, temperature variations, etc.).
Design
1. Conductor
- Flexible stranded tinned copper, class 5 acc. to IEC 60228
- Mineral tape
2. Insulation
- Double layer insulation, rubber type EI110 acc. to EN 50264-3-1
- Colour: black
- Oil, diesel, ozone and UV-resistant
Cable marking
Printing white:
e.g.: FLAMEX 4GKW-EN FR 1,8/3 kV EN 50264-3-1 1800 V (mm²) OM
I NEXANS I WW-YYYY
or
FLAMEX HXAFOE FR 1,8/3 kV EN 50264-3-1 1800 V (mm²) OM
I NEXANS I WW-YYYY
Characteristics
Construction characteristics | |
---|---|
Halogen free | EN 50267-2-1 & EN 60684-2 |
Colour | Black |
Conductor material | Tinned copper |
Conductor flexibility | Flexible stranded |
Sheath colour | Black |
Insulation | EPR |
Dimensional characteristics | |
Conductor cross-section | 70mm² |
Minimum outer diameter | 15.9mm |
Maximum outer diameter | 16.5mm |
Approximate weight | 750kg/km |
Number of cores | 1 |
Electrical characteristics | |
Rated Voltage Uo/U (Um) | 1.8 / 3 kV |
Maximum operating voltage | 2.7kV |
Usage characteristics | |
Fire load | 0.75kWh/m |
Operating temperature, range | -40 .. 90°C |
Smoke density | EN/IEC 61034-2 |
Gases corrosivity | EN 50267-2-2 |
Gases toxicity | EN 50305-9.2 |
Flame retardant | EN 60332-1-2 |
Fire retardant | EN 60332-3-24 & EN 60332-3-25 |
Bending factor when installed | 5(xD) |
Standard | EN |
Bending factor when laying | 10(xD) |
Oil resistance | Yes |
Ozone resistance | Yes |
U.V resistance | Yes |
Docs and info
Electrical properties
Nominal voltage |
Uo/U (Umax) = 1,8/3 (3,6) kV |
Max. operating voltage (d.c.) |
Vo =2,7 kV |
Testing a.c. voltage (5 minutes) |
U = 6,5 kV |
Max. operating temperature at conductor
Conductor at normal operation |
≤ 90 °C/250.000 h |
|
≤ 120 °C/20.000 h |
Conductor under short-circuit conditions (tinned) |
≤ 200 °C |
Selling information
Special conditions relating to temperature and bending radii (e.g. by compelled guidance into cluthes, wagon transition and boogies) on request.