XDCuT 1x630/37 Cu, 30 kV ASE PELD

Description

Description

Standards

  • Product
    HD 620; IEC 60502
  • National
    ASE

Halogenfree medium voltage single-core cable with copper conductor, cross-linked PE insulation (XLPE) and copper screen for underground power networks.

 

Applications

  •  Underground distribution networks
  •  Laying in tubes and direct buried
  •  Arises in electrical substations
  •  Railways

 
 

Key points

  •  Nominal voltage 30 kV

 
 

Construction

  • Copper conductor
  • Inner semi-conductor
  • Cross-linkend PE insulation ( XLPE )
  • Outer semi-conductor
  • Semi-conductive swelling tape
  • Copper screen
  • Outer PE sheath

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Copper
Conductor shape
Circular
Conductor flexibility
Stranded class 2
Material of the inner semi-conductor
Extruded
Insulation
XLPE (chemical)
Material of the external semi-conductor
Extruded
Screen
Copper tape
Outer sheath
Halogen free thermoplastic compound
Sheath colour
Black + 2 red lines

Dimensional characteristics

Dimensional characteristics

Conductor cross-section
630 mm²
Conductor diameter
30.9 mm
Average insulation thickness
6.8 mm
Diameter over insulation
47.5 mm
Screen section
37 mm²
Diameter over external conductor / metallic screen
50.1 mm
Average sheath thickness
2.2 mm
Nominal outer diameter
54.5 mm
Approximate weight
747.1 kg/100m
Number of cores
1

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
18/30 kV
Maximum operating voltage
36 kV
Perm. current rating in air 30°C - trefoil formation
1157 A
Perm. current rating buried 20°C - trefoil formation
945 A
Nominal phase capacitance
0.379 µF / km
A.C. Conductor resist. 50Hz and at 90 °C
0.0405 Ohm/km
Phase reactance 50 Hz - trefoil formation
0.0991 Ohm/km
Max. DC resistance of the conductor at 20°C
0.0283 Ohm/km

Mechanical characteristics

Mechanical characteristics

Maximum pulling force by laying
37.8 kN

Usage characteristics

Usage characteristics

Minimum installation temperature
-5 °C
Bending factor when laying
20 (xD)
Bending factor when installed
15 (xD)
Maximum operating temperature
90 °C
Short-circuit max. conductor temperature
250 °C

Resources

Resources

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close