FE05-C 8X6.0 GB LPE
Certifications and labels
FE05-C 8X6.0 GB LPE
FE05-C NOflamm® is a halogen-free safety cable designed to provide reliable fire protection in buildings, tunnels and escape routes. Its robust construction, water resistance (AD7) and low smoke emission make it a safe choice for installations where personal safety and service continuity are essential. Flexible and durable, it integrates easily into demanding technical environments.
Read more- Nexans ref. : 10562465
Description
Description
Standards
-
ProductEN 50575; EN 60529; IEC 60228
-
TestEN 60754-2; IEC 60332-1-2; IEC 61034
-
NationalSEV TP 20B/3C-d
Applications
FE05-C NOflamm® is intended for installations requiring a high level of fire protection:
- Public and private buildings
- Technical rooms and sensitive areas
- Escape routes
- Fixed circuits up to 0.6/1 kV
- Installations requiring halogen-free, low-smoke cables
Key advantages
- Water-resistant (AD7), suitable for temporary immersion
- Halogen-free: low smoke emission
- Bendind radius : min. 6 times the cable diameter
- Rated voltage 0.6/1 kV
- CPR class Cca s1,d1,a1
By choosing FE05-C NOflamm®, you opt for a reliable, safe and durable cable, suitable for professional installations and critical infrastructures.
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Conductor flexibility
Solid class 1
Conductor material
Copper
Conductor shape
Single wired
Halogen free
Yes
Insulation
PE
Outer sheath
HFFR (Halogen Free Flame Retardant)
Sheath colour
Yellow
With Green/Yellow core
Yes
With smaller neutral conductor
No
Dimensional characteristics
Dimensional characteristics
Number of cores
8
Conductor cross-section
6 mm²
Approximate weight
726 kg/km
Neutral conductor section (when smaller)
- mm²
Nominal outer diameter
18.5 mm
Electrical characteristics
Electrical characteristics
Maximum operating voltage
1000 V
Rated Voltage Uo/U (Um)
0,6/1 kV
Test voltage
3500 V
Usage characteristics
Usage characteristics
Water proof
AD7
Fire load
- MJ/km
Flame retardant
EN 60332-1-2
Maximum operating temperature
90 °C
Minimum installation temperature
-5 °C
Minimum operating temperature
-20 °C
Smoke density
EN 50399
Weather resistance
Good
Resources
Resources
Declaration of Performance
- Declaration of Performance n° : 1000768-CHCD
- Certification Date : 3/1/23
- AVCP (Assessment and Verification of Constancy of Performance) : System 1+
- Notified body : 2658
- Declared performance : Cca-s1,d1,a1