Nexans Low voltage cables type GKN Cu
Nexans Low voltage cables type GKN Cu
LV underground distibution cables with cross-linked HEPR insulation and concentric copper-wire conductor.
Read moreGKN 3 X 10/10 Cure 2LN 0.6/1 kV
Nexans ref. 10152848
- Packaging: m
- Number of conductors: 3
- Conductor cross-section: 10 mm²
- Perm. current rating in air 30°C - trefoil formation: 74 A
- Perm. current rating buried 20°C - trefoil formation: 69 A
- I max. @ 60°C-buried, trefoil, joined, earthing 1pt, LF0.627: 56.1 A
- I max. @ 60°C-buried, trefoil, joined, earthing 1pt, LF1: 53.9 A
- I max. @ 60°C-in the air inside, flat, spaced, earthing 1pt, LF1: 52.6 A
- I max. @ 90°C-buried, trefoil, joined, earthing 1pt, LF0.627: 71.6 A
- I max. @ 90°C-buried, trefoil, joined, earthing 1pt, LF1: 68.9 A
- I max. @ 90°C-in the air inside, flat, spaced, earthing 1pt, LF1: 75.3 A
GKN 3 X 10/10 Cure 0.6/1 kV
Nexans ref. 10152847
- Packaging: m
- Number of conductors: 3
- Conductor cross-section: 10 mm²
- Perm. current rating in air 30°C - trefoil formation: 74 A
- Perm. current rating buried 20°C - trefoil formation: 69 A
- I max. @ 60°C-buried, trefoil, joined, earthing 1pt, LF0.627: 56.1 A
- I max. @ 60°C-buried, trefoil, joined, earthing 1pt, LF1: 53.9 A
- I max. @ 60°C-in the air inside, flat, spaced, earthing 1pt, LF1: 52.6 A
- I max. @ 90°C-buried, trefoil, joined, earthing 1pt, LF0.627: 71.6 A
- I max. @ 90°C-buried, trefoil, joined, earthing 1pt, LF1: 68.9 A
- I max. @ 90°C-in the air inside, flat, spaced, earthing 1pt, LF1: 75.3 A
GKN 3 X 10/10 Curm stranded 0.6/1 kV
Nexans ref. 10152850
- Packaging: m
- Number of conductors: 3
- Conductor cross-section: 10 mm²
- Perm. current rating in air 30°C - trefoil formation: 76 A
- Perm. current rating buried 20°C - trefoil formation: 69 A
- I max. @ 60°C-buried, trefoil, joined, earthing 1pt, LF0.627: 56.2 A
- I max. @ 60°C-buried, trefoil, joined, earthing 1pt, LF1: 54 A
- I max. @ 60°C-in the air inside, flat, spaced, earthing 1pt, LF1: 53.3 A
- I max. @ 90°C-buried, trefoil, joined, earthing 1pt, LF0.627: 71.9 A
- I max. @ 90°C-buried, trefoil, joined, earthing 1pt, LF1: 69.1 A
- I max. @ 90°C-in the air inside, flat, spaced, earthing 1pt, LF1: 76.1 A
GKN 3 X 16/16 Curm stranded 0.6/1 kV
Nexans ref. 10152852
- Packaging: m
- Number of conductors: 3
- Conductor cross-section: 16 mm²
- Perm. current rating in air 30°C - trefoil formation: 101 A
- Perm. current rating buried 20°C - trefoil formation: 90 A
- I max. @ 60°C-buried, trefoil, joined, earthing 1pt, LF0.627: 74.1 A
- I max. @ 60°C-buried, trefoil, joined, earthing 1pt, LF1: 71.1 A
- I max. @ 60°C-in the air inside, flat, spaced, earthing 1pt, LF1: 70.4 A
- I max. @ 90°C-buried, trefoil, joined, earthing 1pt, LF0.627: 94.9 A
- I max. @ 90°C-buried, trefoil, joined, earthing 1pt, LF1: 90.9 A
- I max. @ 90°C-in the air inside, flat, spaced, earthing 1pt, LF1: 100.7 A
GKN 3 X 25/25 Curm stranded 0.6/1 kV
Nexans ref. 10152854
- Packaging: m
- Number of conductors: 3
- Conductor cross-section: 25 mm²
- Perm. current rating in air 30°C - trefoil formation: 133 A
- Perm. current rating buried 20°C - trefoil formation: 115 A
- I max. @ 60°C-buried, trefoil, joined, earthing 1pt, LF0.627: 95.3 A
- I max. @ 60°C-buried, trefoil, joined, earthing 1pt, LF1: 91.2 A
- I max. @ 60°C-in the air inside, flat, spaced, earthing 1pt, LF1: 93.1 A
- I max. @ 90°C-buried, trefoil, joined, earthing 1pt, LF0.627: 122.1 A
- I max. @ 90°C-buried, trefoil, joined, earthing 1pt, LF1: 116.7 A
- I max. @ 90°C-in the air inside, flat, spaced, earthing 1pt, LF1: 132.6 A
GKN 3 X 50/50 Curm stranded 0.6/1 kV
Nexans ref. 10152855
- Packaging: m
- Number of conductors: 3
- Conductor cross-section: 50 mm²
- Perm. current rating in air 30°C - trefoil formation: 200 A
- Perm. current rating buried 20°C - trefoil formation: 170 A
- I max. @ 60°C-buried, trefoil, joined, earthing 1pt, LF0.627: 137.7 A
- I max. @ 60°C-buried, trefoil, joined, earthing 1pt, LF1: 131.1 A
- I max. @ 60°C-in the air inside, flat, spaced, earthing 1pt, LF1: 140.2 A
- I max. @ 90°C-buried, trefoil, joined, earthing 1pt, LF0.627: 176.7 A
- I max. @ 90°C-buried, trefoil, joined, earthing 1pt, LF1: 168.1 A
- I max. @ 90°C-in the air inside, flat, spaced, earthing 1pt, LF1: 200.2 A
GKN 3 X 6/6 Cure 2LN 0.6/1 kV
Nexans ref. 10152845
- Packaging: m
- Number of conductors: 3
- Conductor cross-section: 6 mm²
- Perm. current rating in air 30°C - trefoil formation: 55 A
- Perm. current rating buried 20°C - trefoil formation: 51 A
- I max. @ 60°C-buried, trefoil, joined, earthing 1pt, LF0.627: 42.3 A
- I max. @ 60°C-buried, trefoil, joined, earthing 1pt, LF1: 40.8 A
- I max. @ 60°C-in the air inside, flat, spaced, earthing 1pt, LF1: 38.6 A
- I max. @ 90°C-buried, trefoil, joined, earthing 1pt, LF0.627: 54 A
- I max. @ 90°C-buried, trefoil, joined, earthing 1pt, LF1: 52 A
- I max. @ 90°C-in the air inside, flat, spaced, earthing 1pt, LF1: 55 A
GKN 3 X 6/6 Cure 0.6/1 kV
Nexans ref. 10152843
- Packaging: m
- Number of conductors: 3
- Conductor cross-section: 6 mm²
- Perm. current rating in air 30°C - trefoil formation: 55 A
- Perm. current rating buried 20°C - trefoil formation: 51 A
- I max. @ 60°C-buried, trefoil, joined, earthing 1pt, LF0.627: 42.3 A
- I max. @ 60°C-buried, trefoil, joined, earthing 1pt, LF1: 40.8 A
- I max. @ 60°C-in the air inside, flat, spaced, earthing 1pt, LF1: 38.6 A
- I max. @ 90°C-buried, trefoil, joined, earthing 1pt, LF0.627: 54 A
- I max. @ 90°C-buried, trefoil, joined, earthing 1pt, LF1: 52 A
- I max. @ 90°C-in the air inside, flat, spaced, earthing 1pt, LF1: 55 A
GKN 3 X 95/95 Curm stranded 0.6/1 kV
Nexans ref. 10152858
- Packaging: m
- Number of conductors: 3
- Conductor cross-section: 95 mm²
- Perm. current rating in air 30°C - trefoil formation: 308 A
- Perm. current rating buried 20°C - trefoil formation: 252 A
- I max. @ 60°C-buried, trefoil, joined, earthing 1pt, LF0.627: 207.4 A
- I max. @ 60°C-buried, trefoil, joined, earthing 1pt, LF1: 196.3 A
- I max. @ 60°C-in the air inside, flat, spaced, earthing 1pt, LF1: 215.7 A
- I max. @ 90°C-buried, trefoil, joined, earthing 1pt, LF0.627: 266.8 A
- I max. @ 90°C-buried, trefoil, joined, earthing 1pt, LF1: 252.2 A
- I max. @ 90°C-in the air inside, flat, spaced, earthing 1pt, LF1: 307.9 A
GKN 3 X 150 Cu/95 mm² 0.6/1 kV
Nexans ref. 10152859
- Packaging: m
- Number of conductors: 3
- Conductor cross-section: 150 mm²
- Perm. current rating in air 30°C - trefoil formation: 408 A
- Perm. current rating buried 20°C - trefoil formation: 323 A
- I max. @ 60°C-buried, trefoil, joined, earthing 1pt, LF0.627: 268 A
- I max. @ 60°C-buried, trefoil, joined, earthing 1pt, LF1: 252.5 A
- I max. @ 60°C-in the air inside, flat, spaced, earthing 1pt, LF1: 287.2 A
- I max. @ 90°C-buried, trefoil, joined, earthing 1pt, LF0.627: 345.2 A
- I max. @ 90°C-buried, trefoil, joined, earthing 1pt, LF1: 324.8 A
- I max. @ 90°C-in the air inside, flat, spaced, earthing 1pt, LF1: 410.4 A
GKN 3 X 150/150 Curm stranded 0.6/1 kV
Nexans ref. 10152860
- Packaging: m
- Number of conductors: 3
- Conductor cross-section: 150 mm²
- Perm. current rating in air 30°C - trefoil formation: 408 A
- Perm. current rating buried 20°C - trefoil formation: 323 A
- I max. @ 60°C-buried, trefoil, joined, earthing 1pt, LF0.627: 267.3 A
- I max. @ 60°C-buried, trefoil, joined, earthing 1pt, LF1: 251.9 A
- I max. @ 60°C-in the air inside, flat, spaced, earthing 1pt, LF1: 286.1 A
- I max. @ 90°C-buried, trefoil, joined, earthing 1pt, LF0.627: 344.2 A
- I max. @ 90°C-buried, trefoil, joined, earthing 1pt, LF1: 324 A
- I max. @ 90°C-in the air inside, flat, spaced, earthing 1pt, LF1: 408.2 A
GKN 3 X 240/240 Curm stranded 0.6/1 kV
Nexans ref. 10152862
- Packaging: m
- Number of conductors: 3
- Conductor cross-section: 240 mm²
- Perm. current rating in air 30°C - trefoil formation: 547 A
- Perm. current rating buried 20°C - trefoil formation: 433 A
- I max. @ 60°C-buried, trefoil, joined, earthing 1pt, LF0.627: 356 A
- I max. @ 60°C-buried, trefoil, joined, earthing 1pt, LF1: 333.4 A
- I max. @ 60°C-in the air inside, flat, spaced, earthing 1pt, LF1: 384.6 A
- I max. @ 90°C-buried, trefoil, joined, earthing 1pt, LF0.627: 459.1 A
- I max. @ 90°C-buried, trefoil, joined, earthing 1pt, LF1: 429.5 A
- I max. @ 90°C-in the air inside, flat, spaced, earthing 1pt, LF1: 547.2 A
GKN 4 X 150/150 Curm 0.6/1 kV
Nexans ref. 10511682
- Packaging: m
- Number of conductors: 4
- Conductor cross-section: 150 mm²
- Perm. current rating in air 30°C - trefoil formation: 408 A
- Perm. current rating buried 20°C - trefoil formation: 323 A
- I max. @ 60°C-buried, trefoil, joined, earthing 1pt, LF0.627: 272.3 A
- I max. @ 60°C-buried, trefoil, joined, earthing 1pt, LF1: 255.9 A
- I max. @ 60°C-in the air inside, flat, spaced, earthing 1pt, LF1: 294.1 A
- I max. @ 90°C-buried, trefoil, joined, earthing 1pt, LF0.627: 350.2 A
- I max. @ 90°C-buried, trefoil, joined, earthing 1pt, LF1: 330 A
- I max. @ 90°C-in the air inside, flat, spaced, earthing 1pt, LF1: 419.2 A
GKN 4 X 16/16 Curm 0.6/1 kV
Nexans ref. 10511460
- Packaging: m
- Number of conductors: 4
- Conductor cross-section: 16 mm²
- Perm. current rating in air 30°C - trefoil formation: 101 A
- Perm. current rating buried 20°C - trefoil formation: 90 A
- I max. @ 60°C-buried, trefoil, joined, earthing 1pt, LF0.627: 76.1 A
- I max. @ 60°C-buried, trefoil, joined, earthing 1pt, LF1: 73.1 A
- I max. @ 60°C-in the air inside, flat, spaced, earthing 1pt, LF1: 72.4 A
- I max. @ 90°C-buried, trefoil, joined, earthing 1pt, LF0.627: 96.9 A
- I max. @ 90°C-buried, trefoil, joined, earthing 1pt, LF1: 92.9 A
- I max. @ 90°C-in the air inside, flat, spaced, earthing 1pt, LF1: 103.7 A
GKN 4 X 240/240 Curm 0.6/1 kV
Nexans ref. 10562669 - Country ref. Switzerland
- Packaging: Cut to length (m)
- Number of conductors: 4
- Conductor cross-section: 240 mm²
- Perm. current rating in air 30°C - trefoil formation: 579 A
- Perm. current rating buried 20°C - trefoil formation: 417 A
- I max. @ 60°C-buried, trefoil, joined, earthing 1pt, LF0.627: 362 A
- I max. @ 60°C-buried, trefoil, joined, earthing 1pt, LF1: 338.4 A
- I max. @ 60°C-in the air inside, flat, spaced, earthing 1pt, LF1: 396.6 A
- I max. @ 90°C-buried, trefoil, joined, earthing 1pt, LF0.627: 467.1 A
- I max. @ 90°C-buried, trefoil, joined, earthing 1pt, LF1: 436.5 A
- I max. @ 90°C-in the air inside, flat, spaced, earthing 1pt, LF1: 566.2 A
GKN 4 X 25/25 Curm 0.6/1 kV
Nexans ref. 10511397
- Packaging: m
- Number of conductors: 4
- Conductor cross-section: 25 mm²
- Perm. current rating in air 30°C - trefoil formation: 133 A
- Perm. current rating buried 20°C - trefoil formation: 115 A
- I max. @ 60°C-buried, trefoil, joined, earthing 1pt, LF0.627: 98.3 A
- I max. @ 60°C-buried, trefoil, joined, earthing 1pt, LF1: 93.2 A
- I max. @ 60°C-in the air inside, flat, spaced, earthing 1pt, LF1: 96.1 A
- I max. @ 90°C-buried, trefoil, joined, earthing 1pt, LF0.627: 124.1 A
- I max. @ 90°C-buried, trefoil, joined, earthing 1pt, LF1: 118.7 A
- I max. @ 90°C-in the air inside, flat, spaced, earthing 1pt, LF1: 136.6 A
GKN 4 X 50/50 Curm 0.6/1 kV
Nexans ref. 10512330
- Packaging: m
- Number of conductors: 4
- Conductor cross-section: 50 mm²
- Perm. current rating in air 30°C - trefoil formation: 200 A
- Perm. current rating buried 20°C - trefoil formation: 170 A
- I max. @ 60°C-buried, trefoil, joined, earthing 1pt, LF0.627: 140.7 A
- I max. @ 60°C-buried, trefoil, joined, earthing 1pt, LF1: 133.1 A
- I max. @ 60°C-in the air inside, flat, spaced, earthing 1pt, LF1: 145.2 A
- I max. @ 90°C-buried, trefoil, joined, earthing 1pt, LF0.627: 180.7 A
- I max. @ 90°C-buried, trefoil, joined, earthing 1pt, LF1: 172.1 A
- I max. @ 90°C-in the air inside, flat, spaced, earthing 1pt, LF1: 207.2 A
GKN 4 X 95/95 Curm 0.6/1 kV
Nexans ref. 10511681
- Packaging: m
- Number of conductors: 4
- Conductor cross-section: 95 mm²
- Perm. current rating in air 30°C - trefoil formation: 308 A
- Perm. current rating buried 20°C - trefoil formation: 252 A
- I max. @ 60°C-buried, trefoil, joined, earthing 1pt, LF0.627: 212.4 A
- I max. @ 60°C-buried, trefoil, joined, earthing 1pt, LF1: 200.3 A
- I max. @ 60°C-in the air inside, flat, spaced, earthing 1pt, LF1: 222.7 A
- I max. @ 90°C-buried, trefoil, joined, earthing 1pt, LF0.627: 272.8 A
- I max. @ 90°C-buried, trefoil, joined, earthing 1pt, LF1: 257.2 A
- I max. @ 90°C-in the air inside, flat, spaced, earthing 1pt, LF1: 316.9 A
GKN 4 X 10/10 Cure 3LN 0.6/1 kV
Nexans ref. 10510792
- Packaging: m
- Number of conductors: 4
- Conductor cross-section: 10 mm²
- Perm. current rating in air 30°C - trefoil formation: 74 A
- Perm. current rating buried 20°C - trefoil formation: 69 A
- I max. @ 60°C-buried, trefoil, joined, earthing 1pt, LF0.627: 57.1 A
- I max. @ 60°C-buried, trefoil, joined, earthing 1pt, LF1: 54.9 A
- I max. @ 60°C-in the air inside, flat, spaced, earthing 1pt, LF1: 53.6 A
- I max. @ 90°C-buried, trefoil, joined, earthing 1pt, LF0.627: 72.6 A
- I max. @ 90°C-buried, trefoil, joined, earthing 1pt, LF1: 70.9 A
- I max. @ 90°C-in the air inside, flat, spaced, earthing 1pt, LF1: 77.3 A
GKN 4 X 10/10 Curm 3LN 0.6/1 kV
Nexans ref. 10564611
- Packaging: m
- Number of conductors: 4
- Conductor cross-section: 10 mm²
- Perm. current rating in air 30°C - trefoil formation: 76 A
- Perm. current rating buried 20°C - trefoil formation: 69 A
- I max. @ 60°C-buried, trefoil, joined, earthing 1pt, LF0.627: 57.2 A
- I max. @ 60°C-buried, trefoil, joined, earthing 1pt, LF1: 55 A
- I max. @ 60°C-in the air inside, flat, spaced, earthing 1pt, LF1: 54.3 A
- I max. @ 90°C-buried, trefoil, joined, earthing 1pt, LF0.627: 72.9 A
- I max. @ 90°C-buried, trefoil, joined, earthing 1pt, LF1: 71.1 A
- I max. @ 90°C-in the air inside, flat, spaced, earthing 1pt, LF1: 78.1 A
GKN 4 X 6/6 Cure 0.6/1 kV
Nexans ref. 10512716
- Packaging: m
- Number of conductors: 4
- Conductor cross-section: 6 mm²
- Perm. current rating in air 30°C - trefoil formation: 55 A
- Perm. current rating buried 20°C - trefoil formation: 51 A
- I max. @ 60°C-buried, trefoil, joined, earthing 1pt, LF0.627: 43.3 A
- I max. @ 60°C-buried, trefoil, joined, earthing 1pt, LF1: 41.8 A
- I max. @ 60°C-in the air inside, flat, spaced, earthing 1pt, LF1: 39.6 A
- I max. @ 90°C-buried, trefoil, joined, earthing 1pt, LF0.627: 55 A
- I max. @ 90°C-buried, trefoil, joined, earthing 1pt, LF1: 53 A
- I max. @ 90°C-in the air inside, flat, spaced, earthing 1pt, LF1: 57 A
Description
Description
Standards
-
ProductHD 603; IEC 60228
-
NationalASE
Applications
- Underground distribution networks
- Pipe laying and ground laying
- Installation in electrical substations
Construction
- Copper or aluminium conductor
- Cross-linked HEPR insulation
- Assembly of insulated conductors
- Extruded filler
- Ceander concentric conductor made of copper wire
- Black PE outer sheath with 2 yellow longitudinal stripes
Properties
- Cross-linked insulation with high resistance to high operating temperatures in case of overload and short circuit.
- No release of corrosive gases = safe installation
- Outer sheath made of specially abrasion-resistant PE with low shrinkage rate.
- No interruption of the protective conductor when making a branch
- Halogen-free
Characteristics
Characteristics
Resources
Resources
Our websites
Select your country to find our products and solutions
-
Africa
- Africa
- Ghana
- Ivory Coast
- Morocco
- North West Africa
- Americas
- Asia
- Europe
- Oceania