Nexans Low voltage single core distribution cables type GKN-CU
Nexans Low voltage single core distribution cables type GKN-CU
LV underground distribution single core cables with cross-linked HEPR insulation and concentric copper-wire conductor.
Read moreGKN 1 X 150/50 Curm 0.6/1 kV
Nexans ref. 10152839
- Packaging: m
- Conductor cross-section: 150 mm²
- Perm. current rating in air 30°C - trefoil formation: 410 A
- Perm. current rating buried 20°C - trefoil formation: 360 A
- I max. @ 60°C-buried, trefoil, joined, earthing 1pt, LF0.627: 297.4 A
- I max. @ 60°C-buried, trefoil, joined, earthing 1pt, LF1: 276.6 A
- I max. @ 60°C-in the air inside, flat, spaced, earthing 1pt, LF1: 385.8 A
- I max. @ 90°C-buried, trefoil, joined, earthing 1pt, LF0.627: 384.9 A
- I max. @ 90°C-buried, trefoil, joined, earthing 1pt, LF1: 357 A
- I max. @ 90°C-in the air inside, flat, spaced, earthing 1pt, LF1: 556.6 A
GKN 1 X 240/80 Curm 0.6/1 kV
Nexans ref. 10152840
- Packaging: m
- Conductor cross-section: 240 mm²
- Perm. current rating in air 30°C - trefoil formation: 550 A
- Perm. current rating buried 20°C - trefoil formation: 470 A
- I max. @ 60°C-buried, trefoil, joined, earthing 1pt, LF0.627: 400.7 A
- I max. @ 60°C-buried, trefoil, joined, earthing 1pt, LF1: 369.7 A
- I max. @ 60°C-in the air inside, flat, spaced, earthing 1pt, LF1: 528.8 A
- I max. @ 90°C-buried, trefoil, joined, earthing 1pt, LF0.627: 519.5 A
- I max. @ 90°C-buried, trefoil, joined, earthing 1pt, LF1: 477.7 A
- I max. @ 90°C-in the air inside, flat, spaced, earthing 1pt, LF1: 761.5 A
GKN 1 X 300/100 Curm 0.6/1 kV
Nexans ref. 10152841
- Packaging: m
- Conductor cross-section: 300 mm²
- Perm. current rating in air 30°C - trefoil formation: 630 A
- Perm. current rating buried 20°C - trefoil formation: 530 A
- I max. @ 60°C-buried, trefoil, joined, earthing 1pt, LF0.627: 452.9 A
- I max. @ 60°C-buried, trefoil, joined, earthing 1pt, LF1: 416.7 A
- I max. @ 60°C-in the air inside, flat, spaced, earthing 1pt, LF1: 612.9 A
- I max. @ 90°C-buried, trefoil, joined, earthing 1pt, LF0.627: 588.2 A
- I max. @ 90°C-buried, trefoil, joined, earthing 1pt, LF1: 539.4 A
- I max. @ 90°C-in the air inside, flat, spaced, earthing 1pt, LF1: 884.9 A
Description
Description
Standards
-
ProductHD 603; IEC 60228
-
NationalASE
Applications
- Low voltage distribution networks underground.
- Poses tubes, gutters, cable trays and in earth.
- Arises in electrical substations.
Construction
- Copper conducteur
- Cross-linked HEPR insulation
- Extruded filler
- Concentric copper wire conductor
- Outer PE sheath
Properties
- Cross-linked insulation with high resistance to high operating temperatures in case of overload and short circuit.
- No release of corrosive gases = safe installation
- Outer sheath made of specially abrasion-resistant PE with low shrinkage rate.
- No interruption of the protective conductor when making a branch
- Halogen-free
Characteristics
Characteristics
Resources
Resources
Our websites
Select your country to find our products and solutions
-
Africa
- Africa
- Ghana
- Ivory Coast
- Morocco
- North West Africa
- Americas
- Asia
- Europe
- Oceania