Deutsch français Login Get Registered Catalog Browser Contact Us
Cables, accessories for LV,MV,HV Power and FTTx, copper Telecom networks, cabling Building and Industry - www.nexans.ch – Nexans

About Nexans

Products and Solutions

Customer Service

Work at Nexans

News and Press

Go

XKDT-YT Alu XLPE insulated 3 core cables

Send link to this page print Your Nexans contact on this page
XKDT-YT Alu XLPE insulated 3 core cables International Designation  NA2XHS(F)2Y-2Y

Three-core cables with aluminium conductors, cross-linked PE insulation (XLPE), copper-wire screens and triangular protection sheath.

Conductor cross-sections of 95 mm² up to 400 mm².

Other voltage levels or conductor cross-sections on request.

Standards
International  HD 620; IEC 60502
National  ASE
Description

Halogenfree three-core cables with aluminium conductors, cross-linked PE insulation ( XLPE), copper-wire screens and triangular protection sheath for medium voltage underground networks.
 

 

Applications

  • Underground distribution networks
  • Laying in tubes and direct buried
  • Arises in electrical substations

 
 

Key points

  • Nominal voltage 10 kV / 20 kV / 30 kV
  • Lead sections 95 to 400 mm2

 
 

Construction three-core cables

  • Assembly of 3 XLPE insulated single core cables
  • Outer HDPE-sheath
     

Construction single core cables

  • Aluminium conductor
  • Inner Semiconductor
  • Cross-linkend PE insulation (XLPE)
  • Outer semi-conductor
  • Semi-conductive swelling tape
  • Copper wire screen
  • Swelling tape
  • Outer PE sheath

 TOP
Characteristics
Construction characteristics
Conductor material Aluminium/polyester tape  
Conductor shape Round, stranded  
Conductor flexibility Stranded class 2  
Insulation XLPE  
Material of the outer core / screen Copper wires  
Outer core type Waveform concentric  
Inner sheath LLDPE  
Outer sheath PE-HD  
Sheath colour Black + 2 red lines  
Halogen free PE  
Dimensional characteristics
Number of cores 3  
Electrical characteristics
Rated Voltage Uo/U (Um) 12/20 kV  
Maximum operating voltage 24kV  
Test voltage 48kV  
Impulse voltage 125kV  
Usage characteristics
Maximum operating temperature 90°C  
Short-circuit max. conductor temperature 250°C  
Field of application Indoor, Outdoor, Underground  

 TOP
Results   4/4
Select all Items Nexans ref. Name Cross section (mm²)
10152610 XKDT-YT 3x1x 95 Alrm / 16 CuK mm² 12/20kV 95
10152611 XKDT-YT 3x1x150 Alrm / 25 CuK mm² 12/20kV 150
10152613 XKDT-YT 3x1x240 Alrm / 35 CuK mm² 12/20kV 240
Make to order product 10182717 XKDT-YT 3x1x400 Alrm / 35 CuK mm² 12/20kV 400
Add to favorites

 TOP
Accessories for MV cables

Nexans © copyright 2001 - 2012   Legal Notice | Contact Us | Site Map