XKDT Alu XLPE Insulated cables

Send link to this page print Your Nexans contact on this page
XKDT Alu XLPE Insulated cables International Designation  NA2XHS(F)2Y

Single-core cables with aluminium conductor, cross-linked PE insulation (XLPE) and copper-wire screen.

Conductor cross-section of 50 mm² up to 800 mm².

Other voltage levels or conductor cross-section on request.

Standards
International  HD 620; IEC 60502
National  ASE
Description

20 kV single-core cables with aluminium conductor, cross-linked PE insulation (XLPE) and copper-wire screen for medium voltage underground power networks.

 

Applications

  •  Underground distribution networks
  •  Laying in tubes and direct buried
  •  Arises in electrical substations

 

Key points

  •  Nominal voltage 10 kV / 20 kV / 30 kV
  •  Lead sections 25 to 630 mm2

 

Construction

  • Aluminium conductor
  • Inner semi-conductor
  • Cross-linked PE insulation (XLPE)
  • Outer semi-conductor
  • Semi-conductiveswelling tape
  • Copper-wire screen
  • Swelling tape
  • Outer PE sheath

 TOP
Characteristics
Construction characteristics
Conductor material Aluminium/polyester tape  
Conductor shape Circular  
Conductor flexibility Stranded class 2  
Insulation PRC  
Material of the outer core / screen Copper wires  
Outer sheath PE LLD  
Sheath colour Black + 2 red lines  
Halogen free PE  
Electrical characteristics
Rated Voltage Uo/U (Um) 12/20 kV  
Test voltage 48kV  
Impulse voltage 125kV  
Maximum operating voltage 24kV  
Usage characteristics
Maximum operating temperature 90°C  
Short-circuit max. conductor temperature 250°C  
Field of application Indoor, Outdoor, Underground  

 TOP
Results   7/7
Select all Items Nexans ref. Name Cross section (mm²)
Make to order product 10221202 XKDT 1x 50 Alrm / 10 CuK mm² 12/20 kV 50
10152605 XKDT 1x 95 Alrm / 16 CuK mm² 12/20 kV 95
10152606 XKDT 1x150 Alrm / 25 CuK mm² 12/20 kV 150
10152607 XKDT 1x240 Alrm / 35 CuK mm² 12/20 kV 240
10216057 XKDT 1x300 Alrm / 35 CuK mm² 12/20 kV 300
10152608 XKDT 1x400 Alrm / 35 CuK mm² 12/20 kV 400
10168129 XKDT 1x500 Alrm / 35 Cuk mm² 12/20 kV 500
Add to favorites