XKDT-YT XLPE insulated 3 core cables

Send link to this page print Your Nexans contact on this page
XKDT-YT XLPE insulated 3 core cables International Designation  N2XHS(F)2Y-2Y

three-core cables with cross-linked PE insulation (XLPE), copper-wire screens and triangular protection sheath.

Conductor cross-sections of 50 mm² to 240 mm².

Other voltage levels or conductor cross-sections on request

Standards
International  HD 620; IEC 60502
National  ASE
Description

Halogenfree three-core cables with copper conductors, cross-linked PE insulation (XLPE), copper-wire screens and triangular protection sheath for underground medium voltage networks.

 

Applications

  • Underground distribution networks
  • Laying in tubes and direct buried
  • Arises in electrical substations

 
 

Key points

  • Nominal voltage 10 kV / 20 kV / 30 kV
  • Lead sections 50 to 240 mm2

 
 

Construction three-core cables

  • Assembly of 3 XLPE insulated single core cables
  • Outer HDPE-sheath

 

Construction single core cables

  • Copper conductor
  • Inner Semiconductor
  • Cross-linkend PE insulation (XLPE)
  • Outer semi-conductor
  • Semi-conductive swelling tape
  • Copper wire screen
  • Swelling tape
  • Outer PE sheath

 TOP
Characteristics
Construction characteristics
Conductor material Aluminium / Polyester tape  
Conductor shape Circular  
Conductor flexibility Stranded class 2  
Insulation PRC  
Material of the outer core / screen Copper wires  
Outer core type Waveform concentric  
Inner sheath LLDPE  
Outer sheath Tinned copper drain wire + aluminium/polyester tape  
Sheath colour Black + 2 red lines  
Halogen free PE  
Armour type 1 x 16 mm²  
Dimensional characteristics
Number of cores 3  
Electrical characteristics
Rated Voltage Uo/U (Um) 12 / 20 (24) kV  
Maximum operating voltage 24kV  
Test voltage 48kV  
Impulse voltage 125kV  
Usage characteristics
Maximum operating temperature 90°C  
Short-circuit max. conductor temperature 250°C  
Field of application Indoor, Outdoor, Underground  

 TOP
Results   4/4
Select all Items Nexans ref. Name Cross section (mm²)
10152594 XKDT-YT 3x1x 50/16 mm² 12/20 kV 50
10152597 XKDT-YT 3x1x 95/25 mm² 12/20 kV 95
10152600 XKDT-YT 3x1x150/35 mm² 12/20 kV 150
Make to order product 10152601 XKDT-YT 3x1x240/35 mm² 12/20 kV 240