XDAluT XLPE insulated cables International Designation  N2XHKL2Y
Single-core cables with cross-linked PE insulation (XLPE) and extruded aluminium sheath.

Standards
International  HD 620; IEC 60502
National  ASE
Description

 Halogenfree single-core cables with cross-linked PE insulation (XLPE) and extruded aluminium sheath.

 

Applications

  • Underground distribution networks
  • Laying in tubes and direct buried
  • Arises in electrical substations

 

Key-points

  • Rated voltages 10 kV / 20 kV / 30 kV
  • Conductor cross sections 25 mm2 up to 630 mm2
  • Idealy adapted for laying in lakes and thanks to its low screen resistance it is suitable for rocky areas exposed to lightnîng.

 

Construction

  • Copper conductor
  • Inner semi-conductor
  • Cross-linked PE insulation ( XLPE )
  • Outer semi-conductor
  • Semi-conductive swelling tapes
  • Extruded aluminium screen
  • Outer HDPE sheath

 

Key points of seamless extruded aluminum sheath

  • radial sealing guaranted (eg. laying for lake)
  • allows important clamping radial forces
  • good mechanical protection of cable
  • excellent protection of electrical cable.
  • Where lightening danger exists, the good condutivity of the sheath provides optima ground connection and avoids damages duc to over voltages

 TOP
Characteristics
Construction characteristics
Conductor material Aluminium / Polyester tape  
Conductor flexibility Stranded class 2  
Insulation Polyester tape separator  
Material of the outer core / screen Smooth extruded aluminium  
Halogen free PE  
Radial waterproof Yes  
Dimensional characteristics
Number of cores 1  
Electrical characteristics
Rated Voltage Uo/U (Um) 12 / 20 (24) kV  
Maximum operating voltage 24kV  
Test voltage 48kV  
Impulse voltage 125kV  
Usage characteristics
Maximum operating temperature 90°C  
Short-circuit max. conductor temperature 250°C  
Water proof Longitudinal & radial  
Field of application Indoor, Outdoor, Underground  

 TOP
Results   4/4
Select all Items Nexans ref. Name Cross section (mm²)
Make to order product 0615036000 XDALUT 1x 50 mm² 12/20 kV 50
Make to order product 10152639 XDALUT 1x 95 mm² 12/20 kV 95
Make to order product 10152640 XDALUT 1x150 mm² 12/20 kV 150
Make to order product 10152642 XDALUT 1x240 mm² 12/20 kV 240